LV Switchgear
GCK Low-Voltage Withdrawable Switchgear

GCK Low-Voltage Withdrawable Switchgear

GCK low-voltage withdrawable switchgear combines power distribution and motor control in drawer-type functional units. Designed for industrial power centres and motor control centres, it groups feeder and motor-starter circuits within a common assembly. Individual units can be withdrawn for inspection or replacement in accordance with the equipment's operating procedures.

The documented configuration serves AC 400/660 V systems, with horizontal busbars up to 5,000 A and 50 or 80 kA short-time withstand ratings for 1 second. IP30 and IP40 enclosures are available. Incoming circuits, feeders, protection and controls follow the project single-line diagram.

Technical Specifications

Rated Operating VoltageAC 400 / 660 V
Rated Insulation Voltage660 / 1000 V
Rated Frequency50 Hz
Horizontal Busbar Currentup to 5000 A
Vertical / Branch Busbar Current630 / 1000 / 1250 / 1600 A (branch busbar)
Short-Time Withstand Current50 / 80 kA (1 s) (main busbar)
Peak Withstand Currentup to 176 kA (main busbar)
Enclosure IP RatingIP30 / IP40
StandardsGB 7251.1-2005 / IEC 60439.1-1992

Key Features

  • Drawer-type functional units.
  • High current capacity.
  • Flexible configuration.
  • For PC & MCC applications.

Typical Applications

  • Steel rolling mills and petrochemical plants
  • Ports and docks
  • Hotels and large buildings

Installation & Aftercare

Prepare the site, plan routine checks and keep service records.

What needs to be ready before installation?

  • Catalogue normal conditions: indoor ambient -5 to +40 °C, 24-hour average at most +35 °C, altitude at most 2000 m.
  • Provide a level base, front drawer-handling space and cable routes that remain accessible after the lineup is connected.
  • At +40 °C, catalogue relative humidity is limited to 50%; control condensation and exclude conductive dust or corrosive gases.

What should operators check during routine rounds?

  • Review feeder loading and trip indications during rounds; look for blocked ventilation, condensation and abnormal operating noise.

What is covered during planned maintenance?

  • At planned isolation, qualified personnel inspect drawer power contacts, secondary plugs, interlocks and cable terminations for wear or overheating.
  • After a fault or stiff drawer operation, inspect the affected unit before reuse; use the specified contact-care products and procedure.

Customization Options

Define the electrical configuration and the details needed for your site.

Circuit lineup
Incoming, bus-coupler, distribution and motor-control sections to the single-line diagram.
Busbars & fault duty
Main and vertical busbar ratings, neutral arrangement and verified short-circuit duty.
Protection & motor control
Breaker trip functions, motor-starting method, overload protection and control voltage.
Withdrawable units
Drawer sizes and circuit allocation, spare ways, secondary plugs and interlock requirements.
Cable entry & metering
Top or bottom cable routes, terminal space, metering points and requested communication interfaces.

Project-specific options and accessories are confirmed in the quotation and approved drawings.