LV Switchgear
GCS Low-Voltage Withdrawable Switchgear

GCS Low-Voltage Withdrawable Switchgear

GCS low-voltage withdrawable switchgear provides power distribution and centralised motor control for industrial and infrastructure projects. Its drawer-type units bring feeder and control circuits together in a compact assembly, allowing the cabinet lineup to accommodate the circuit mix required by the installation.

Designed for AC 400/660 V systems, the series offers current ratings up to 5,000 A and IP30 or IP40 enclosure options. Withdrawable-unit functions, control interfaces and cable access are configured to suit the electrical design and available switchroom space, with short-circuit ratings selected for the network fault level.

Technical Specifications

Rated Operating VoltageAC 400 / 660 V
Rated Insulation Voltage660 V
Rated Frequency50 / 60 Hz
Horizontal Busbar Currentup to 5000 A
Vertical / Branch Busbar Current1000 A (vertical MCC busbar)
Short-Time Withstand Current50 / 80 kA (1 s) (main busbar)
Peak Withstand Current105 / 176 kA (main busbar)
Power-Frequency Withstand Voltage2.5 kV (1 min, main circuit); 2 kV (1 min, auxiliary circuit)
Enclosure IP RatingIP30 / IP40
StandardsGB 7251 / IEC 439-1

Key Features

  • Withdrawable drawer units — high flexibility.
  • High current and short-circuit capacity.
  • For PC and MCC applications.
  • Compact, high component density.

Typical Applications

  • Power stations
  • Petrochemical, metallurgical and textile plants
  • High-rise buildings

Installation & Aftercare

Prepare the site, plan routine checks and keep service records.

What needs to be ready before installation?

  • Install in an indoor electrical room with a level foundation and working space for full drawer travel.
  • Coordinate top or bottom cable entry with the supplied lineup drawings; leave room for cable bends and outgoing terminations.
  • Provide room ventilation for the actual losses and control condensation around cable trenches and lightly loaded sections.

What should operators check during routine rounds?

  • Record section loading, overload trips and abnormal temperature indications, particularly where several motors operate together.

What is covered during planned maintenance?

  • During isolated servicing, inspect drawer contacts, secondary connections, interlocks and motor-control devices for wear, contamination or heat damage.
  • Clean ventilation openings and check fitted cooling devices; review protection settings whenever a motor or feeder duty changes.

Customization Options

Define the electrical configuration and the details needed for your site.

Circuit lineup
Incoming, bus-coupler, distribution and motor-control sections to the single-line diagram.
Busbars & fault duty
Main and vertical busbar ratings, neutral arrangement and verified short-circuit duty.
Protection & motor control
Breaker trip functions, motor-starting method, overload protection and control voltage.
Withdrawable units
Drawer sizes and circuit allocation, spare ways, secondary plugs and interlock requirements.
Cable entry & metering
Top or bottom cable routes, terminal space, metering points and requested communication interfaces.

Project-specific options and accessories are confirmed in the quotation and approved drawings.